Marine wire size calculator

The smallest wire that carries your circuit's current without overheating and without losing too much voltage on the way — for any 12, 24 or 48 V circuit on a boat, in AWG and mm².

Your circuit

System voltage
The calculation uses the round trip — out on the positive and back on the negative.
What the circuit feeds
Minimum wire size
6AWG≈ 13.3 mm²

Set by voltage drop. Metric cable: 10 mm² (2.87 % drop).

Voltage drop
0.26 V · 2.16 %
Allowable current
120 A
Circuit length
10 m
Sizemm²AllowableDropResult
18 AWG0.8220 A34.91 %Too much drop
16 AWG1.3125 A21.96 %Too much drop
14 AWG2.0835 A13.81 %Too much drop
12 AWG3.3145 A8.68 %Too much drop
10 AWG5.2660 A5.46 %Too much drop
8 AWG8.3780 A3.43 %Too much drop
6 AWG13.3120 A2.16 % OK
4 AWG21.15160 A1.36 % OK
3 AWG26.67180 A1.08 % OK

Allowable current from 33 CFR 183.425 Table 5; voltage drop for stranded copper at the cable temperature chosen. A planning aid — check the cable maker's ratings and the standard that applies to your boat.

How it works: two checks, the larger wire wins

ABYC's E-11 standard requires a boat's DC conductors to meet both their required ampacity and the applicable voltage-drop limit; when the two give different sizes, the larger one is used. The calculator does both:

  1. Heat (allowable current). From Table 5 of US Coast Guard regulation 33 CFR 183.425, by AWG size and insulation rating, multiplied by the table's correction for engine spaces (0.85 for 105 °C insulation) and for bundles of three or more current-carrying conductors (0.70 for three, down to 0.40 for 25 or more).
  2. Voltage drop. Current × copper resistance over the round trip, as a percentage of the system voltage, against ABYC's limits.

ABYC's voltage-drop limits

Maximum dropFor
3 %Panelboard main feeders, bilge blowers, electronic equipment, navigation lights, and other circuits where drop should be kept to a minimum
10 %Lighting other than navigation lights, and other circuits where drop isn't critical

At 12 V, 3 % is just 0.36 V — which is why long runs on a 12 V boat end up with much thicker wire than the current alone needs. The same load at 24 or 48 V draws a half or a quarter of the current and allows twice or four times the volts of drop.

Worked example

A 20 A load, 5 m from the panel on a 12 V boat, on a 3 % circuit: the round trip is 10 m. 18 AWG would carry 20 A without overheating (with 105 °C insulation), but drops far too much voltage. 8 AWG drops 3.4 %; 6 AWG drops 2.2 %, so 6 AWG it is — or 10 mm² metric cable, at 2.9 %. Voltage drop, not heat, decides almost every long, low-voltage run.

Propulsion cables

Main battery and motor cables carry hundreds of amps, often beyond 4/0 AWG. For those, the configurator sizes the cable with the rest of the propulsion system, and the cable sizing guide and DC safety guide cover fusing and the parts around it.

Questions

How do I choose the wire size for a boat circuit?

Check two things and use the larger wire: the allowable current (ampacity) for the wire's size, insulation rating and location, and the voltage drop over the round-trip length. ABYC's limit is 3 % for panel main feeders, bilge blowers, electronics and navigation lights, and 10 % for other lighting and non-critical circuits.

Is the length one way or round trip?

Voltage drop uses the round trip: from the positive source to the load and back to the negative. Enter the one-way distance in the calculator; it doubles it.

What is the allowable current of marine wire?

This calculator uses Table 5 of US Coast Guard regulation 33 CFR 183.425, which lists allowable amperage by AWG size and insulation temperature rating. For example, 10 AWG with 105 °C insulation is rated 60 A outside engine spaces. In an engine space it's multiplied by 0.85, and bundles of three or more current-carrying conductors take a further correction.

What metric cable size matches an AWG size?

The calculator shows each AWG size's cross-section in mm² and suggests the smallest standard metric size that meets the voltage drop and has at least the cross-section of the AWG size the ampacity table requires.