Battery bank calculator

Put cells — or whole batteries — in series and parallel and see the bank you get: its voltage from empty to full, capacity, energy, current and weight, and whether your motor controller, inverter and charger can work with it.

Build from

Per cell: 3.2 V nominal, charge to 3.55 V, maximum 3.6 V, cut-off 2.8 V — from Victron Lithium NG. Use your own cell's datasheet figures with “Custom” if they differ.

In series
Adds voltage
In parallel
Adds capacity and current
System:
Check against your equipment

The DC input range of your motor controller, inverter or charger, from its datasheet.

16S1P · 16 cells
Nominal
51.2 V
Capacity
280 Ah
Energy
14.34 kWh
44.8 V empty51.2 V nominal57.6 V max

The bank

Voltage window
44.8 V empty – 56.8 V charging – 57.6 V maximum
Cells in series
16 — the BMS must monitor this many
−+

16 in series × 1 in parallel. Each row is a string; strings join at the busbars.

Checks

  • Enter your equipment's input range on the left to check the voltage window against it.

How it works

  • Voltage = units in series × each unit's voltage, at every point of the window: nominal, empty (cut-off), charging and maximum.
  • Capacity = units in parallel × each unit's Ah. Energy = nominal voltage × capacity.
  • Current = strings in parallel × each unit's continuous rating. Power is worked out at the empty voltage, where the same current carries the least power.
  • Batteries are treated as their cells in series — a 12.8 V LiFePO₄ battery as four cells — so the window scales the same way.

Common LiFePO₄ banks

SystemCells in seriesNominalEmpty (2.8 V)Charge (3.55 V)
12 V412.8 V11.2 V14.2 V
24 V825.6 V22.4 V28.4 V
48 V1651.2 V44.8 V56.8 V
96 V32102.4 V89.6 V113.6 V

Per-cell figures from Victron's Lithium NG documents. A 96 V propulsion bank swings from about 90 V empty to 114 V charging — check that against every piece of equipment on it.

Before you build

  • The BMS must monitor every cell in series: a REC 2Q, for example, handles 4 to 16.
  • Cells in a bank should be the same model, capacity and age, at the same state of charge when assembled.
  • Batteries with their own BMS: follow the maker's maximum in series and in parallel.
  • Fuse and switch the bank, size every cable for its current, and protect parallel strings.

The battery bank wiring guide covers series, parallel and string fusing; the BMS guide and DC safety guide the parts around it. Size the cables with the wire size calculator, and see how far the bank goes with the range calculator.

Questions

What do series and parallel do to a battery bank?

Series adds voltage and leaves capacity (Ah) unchanged; parallel adds capacity and current and leaves voltage unchanged. Either way the energy, voltage × Ah, adds up. Four 12.8 V 100 Ah batteries make 51.2 V 100 Ah in series or 12.8 V 400 Ah in parallel: 5.12 kWh both ways.

How many LiFePO₄ cells make a 48 V battery?

Sixteen in series. At 3.2 V nominal per cell that is 51.2 V — what's sold as a 48 V LiFePO₄ battery. Victron's 51.2 V Lithium NG charges at 56–56.8 V and switches loads off at 44.8 V, 2.8 V per cell.

Why does the voltage window matter?

Your motor controller, inverter and charger each accept a range of DC input voltage. The bank must stay inside it from empty to full: too low and the equipment cuts out before the bank is empty; too high and a full bank can exceed its limit.

Can I put batteries with their own BMS in series?

Only if the maker allows it, and only up to their limit. When one battery's BMS disconnects, the full bank voltage can appear across it. Victron's 51.2 V Lithium NG is for parallel connection only; Torqeedo allows its Power 48-5000 as one battery or two in parallel.