Electric boat cable sizing: the complete guide

Cable sizing is the most under-discussed part of an electric boat installation — and the part most likely to cause a fire, a failed motor controller, or premature battery degradation.

The core problem: DC current in a propulsion system is very high. A 10 kW motor on a 48 V system draws over 200 A at full throttle. At those currents, even small errors in cable size or connection quality generate significant heat.

→ Get your DC current, cable length, and drop % calculated automatically →


Why voltage drop matters more than heat

Most wiring guides focus on thermal limits — the maximum current a cable can carry before the insulation degrades. That matters, but for boat propulsion there is a second and often more important constraint: voltage drop.

At 48 V, a 3% voltage drop across the main cable represents 1.44 V. That 1.44 V appears as reduced voltage at the motor controller input. Motor controllers typically have a low-voltage cutoff; if voltage sags during a hard manoeuvre, the controller may trip and cut power exactly when you need it most — entering a berth, for instance.

The formula:

Voltage drop (V) = Current (A) × Resistance (Ω)
Resistance (Ω) = (Resistivity × Length × 2) ÷ Cross-section

The factor of 2 accounts for both the positive and return conductor. The run length is the one-way distance from battery to motor controller.


Choosing cable cross-section

The table below gives minimum recommended cross-sections for common run lengths at 48 V, assuming copper conductor at 20 °C — derate by ~10% for runs in enclosed hot spaces.

Two constraints apply at once, and the cable has to satisfy both: it must carry the current without overheating (ampacity), and it must not drop too much voltage. At short runs ampacity governs; at long runs voltage drop governs. These figures take whichever is larger, and land around 1% drop — comfortably inside the 3% limit rather than exactly on it. Sizing to exactly 3% would give noticeably thinner cable and leave nothing for terminal resistance, a hot bilge, or a motor you upgrade later.

Continuous current2 m run4 m run6 m run8 m run
100 A16 mm²25 mm²35 mm²50 mm²
150 A25 mm²35 mm²50 mm²70 mm²
200 A35 mm²50 mm²70 mm²95 mm²
250 A50 mm²70 mm²95 mm²120 mm²
300 A70 mm²95 mm²120 mm²150 mm²

At 96 V the same power draws half the current, so read the row for half your amps — a 200 A draw at 48 V becomes 100 A at 96 V and the cross-section falls accordingly. That is the single biggest practical argument for the higher bus voltage.


Marine cable vs automotive cable

Use tinned copper, marine-grade, flexible cable rated for at least 105 °C insulation. This matters for three reasons:

  1. Tinned copper resists the corrosion that untinned cables develop in the bilge environment within a season.
  2. Flexible (stranded fine-wire) construction is essential wherever the cable moves or bends, including anywhere near the motor or battery terminals.
  3. 105 °C rated insulation gives a meaningful safety margin in a bilge that can reach 50–60 °C in summer.

Do not use automotive or household cable in marine propulsion applications. The consequences of a wiring failure at 200 A are severe.


Fusing

48 V PACKLiFePO₄CLASS-TCONTACTORPRE-CHARGE+ BUSBAR− BUSBARMOTOR CONTROLLER3-phase outCHARGERAC inDC-DC12 V houseBMSfailsafe open
DC positiveDC negativeBMS control
DC-side architecture. The Class-T fuse goes within half a metre of the pack positive — everything downstream is protected by it, and the short unprotected stub between pack and fuse is the one length of cable on the boat that must be mechanically faultless. The pre-charge resistor bypasses the contactor so the controller's capacitors are not charged through the main contacts.

Every battery positive must be protected by a fuse or circuit breaker rated for the battery's short-circuit current, not just the motor's operating current. For LiFePO₄ packs, short-circuit current can exceed 2,000 A for even a brief fault.

For a lithium propulsion pack, use a Class T fuse. This matters more than the rating: what counts in a bolted fault is the fuse's interrupting capacity, and an LFP pack can deliver 5,000–20,000 A. Class T is rated to interrupt 20 kA at 125 V DC. MIDI and ANL fuses are rated far below that and can fail to clear the fault — arcing instead of breaking it — which is the one failure mode you are fitting the fuse to prevent. ANL is acceptable on light house circuits; it is not the right part on a propulsion pack.

Placement follows ABYC E-11: overcurrent protection within 7 in (178 mm) of the battery positive terminal, extendable to 40 in (1.02 m) only where the conductor runs inside a sheath or enclosure for its whole length. The fuse protects the cable from the battery, not the motor from itself — so the short stub between post and fuse is the one length on the boat that is unprotected, and it has to be mechanically faultless.


Terminal connections

At high DC current, a poor terminal connection is effectively a resistor in series with your propulsion circuit. A 5 mΩ contact resistance at 200 A dissipates 20 W of heat — enough to soften solder joints and eventually fail.

Use hydraulically crimped lugs rather than soldered or mechanically compressed connections for cables above 35 mm². Solder joints under high current vibration fatigue and crack. Hydraulic crimps make permanent cold-welds that do not loosen.

Torque all terminal fasteners to specification and apply a light coat of non-conductive dielectric grease at each connection to prevent oxidation.


Common wiring mistakes to avoid


Calculating your own cable spec

The inputs you need:

  1. Continuous motor current (A) — from your motor datasheet or the spec calculator
  2. One-way cable run length (m) — measured from battery terminals to motor controller
  3. Bus voltage (V)

With those three numbers, the spec calculator outputs cross-section, estimated voltage drop, and the correct fuse rating.

→ Calculate your cable spec now →

Want exact numbers for your boat?

Use the configurator to generate a vendor-ready spec sheet.

Start the configurator
TPublished by TMHMarch 20, 2026
About TMH & methodology